Duplex Controller: Model DUP-120-023P

The Duplex Controller is a microprocessor based dual (2) pump controller which can alternate between two (2) pumps and detect a high  level alarm. It has the ability to select either pump as the lead or lag pump or alternate between either pump. Built-in time delays prevent both pumps from  turning on or off at the same time.  The duplex controller requires a minimum of four (4) float switch inputs.

Features:

Specifications:

  • Alternates Two (2) Output Loads
  • High Level Alarm
  • Senses Zero Crossing to Reduce Noise Spikes
  • AC or DC Load Output Control
  • Full LED Indication
  • Self Test Function
  • Low Power Input
  • Ground Fault Isolation

Model Number:

DUP-120-023P

Supply Voltage

110 VAC

Power Consumption

Less Than 2 Watts

Transient Protection

Line Input

1500 VAC

Pump Output

4500 VAC

Alarm Output

4500 VAC

Ground Isolation

1500 VAC

Float Switch Type

Normally Open

Float Switch Current @ 5 VDC

1 MA.

All Relay Contacts

Normally Open

Relay Contacts Current @ 110 VAC Res.:

Alarm

8 AMP

Pump

8 AMP

Time Delay

4 Seconds

Operating Temp

-20C to +70C

 

Duplex Controller Part Numbers

Part Number

Supply Voltage

Mounting Configuration

Socket

DUP-120-023P

120 VAC

12 Pin Plug-In

SD12-PC

Theory of Operation

The Duplex Controller accepts float switch inputs or level sensor inputs. The float switch inputs are connected to a normally open float switch with a maximum closed contact resistance of 200 ohms @ 5 VDC.